EasyManua.ls Logo

Lenze E82ZAFIC001 - Wiring with a Host (Master)

Lenze E82ZAFIC001
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Electrical installation
Wiring with a host (master)
5
l
20
EDS82ZAFIC EN 2.0
5.2.2 Wiring with a host (master)
GG
+
E82ZAFICxxx
GG
+
E82ZAFICxxx
GG
+
E82ZAFICxxx
400 m
400 m
1
222
3
3
3
E82ZAFI008
No. Element Description
1 Host E.g. PC or PLC with INTERBUS master interface module
2 Bus cable Connects the INTERBUS master interface module to the function modules.
3 INTERBUS slave Applicable standard device (^ 10) with function module.
l Set DIP switch S1 ( ^ 29):
Setting for the last node = OFF
Setting for all other nodes = ON
Specification of the transmission cable
General characteristics
Cable type Sold by the meter,
(e.g. PHOENIX CONTACT: IBS RBC Meter−T, Order No. 28 06 28 6)
Number of conductors 3 × 2, twisted pairs, with shared shield
Conductor cross−section > 0.2 mm
2
DC cable resistance < 96 W/km
Impedance (characteristic) l 120 W ± 20 % (f = 64 kHz)
l 100 W ±15 W (f > 1 MHz)
Capacitance per unit length < 60 nF/km (f = 800 Hz)