Commissioning
Defining the user data length
6
l
30
EDS82ZAFIC EN 2.0
6.5 Defining the user data length
The number of process data words (PCD) and parameter data words (PCP) can be set via
code C1515 or via the DIP switches S2 ... S4.
) Note!
ƒ Sum of all data words (PZD + PCP): max. 4 words
ƒ Switch off the voltage supply of the function module and the controller and
then on again to activate the changed settings.
Settings via DIP switches S2 ... S4
ON
OFF
1
ON
234
E82ZAFI009
ƒ If one of the DIP switches S2 ... S4 is set to OFF, the configurations resulting from all
switch positions are active at switch−on.
ƒ If the switch positions are invalid, the Lenze setting is activated:
– DIP switches S2 ... S4 = OFF (2 PCD words + 1 PCP word)
ƒ Code C1525 displays the current settings of the DIP switches S2 ... S4.
DIP switch
Value Number of process data
words (PCD)
Number of parameter
data words (PCP)
ID code
S2 S3 S4
OFF OFF OFF 0 2 1 227
ON OFF OFF 1 3 1 227
OFF OFF ON 4 2 0 3
ON OFF ON 5 4 0 3
ON ON ON Code C1515 active.