10.2 Monitoring
C1513:
Response monitoring time of the PCD communication
Code
C1513
Name
Response monitoring time of the PCD communication
Index
0x5A16 (23062)
Subcode Lenze Values Access Data type
65535 0 [1 ms] 65535 rw FIX32
þ Parameter set transfer
Monitoring starts with the arrival of the first telegram.
If there is no message from the master within the response monitoring time set, the
response set in C1514 is carried out.
) Note!
A change of monitoring will be effective immediately.
The value 65535 switches off the response monitoring time.
C1514:
Monitoring response to PCD communication fault
Code
C1514
Name
Monitoring response to PCD communication fault
Index
0x5A15 (23061)
Subcode Lenze Values Access Data type
−0
0 No action
rw
FIX32
1 TRIP (trouble)
2 CINH (controller inhibit)
3 QSP (quick stop)
þ Parameter set transfer
If there is no message from the master within the response monitoring time (configurable
in C1513), the response set in this code is carried out.
) Note!
A change of the monitoring response will be effective immediately.