Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
7
l
36
EDS82ZAFIC EN 2.0
7.1.2 Process data signals for 8200 vector / 8200 motec
Configuring process output data
The assignment of the max. 4 process output data words (POW) of the master to bit control
commands or setpoints of the controller can be configured freely using C1511.
ƒ In order to activate the DRIVECOM device control, assign the DRIVECOM control
word to a POW (C1511/x = 17).
The DRIVECOM control word is mapped to the FIF control word 1.
The controller conforms to the DRIVECOM state machine ( 42).
ƒ The FIF control words can be used to set up an extended Lenze device control
( 38).
) Note!
When C1511 is changed, the process output data is automatically locked to
ensure data consistency. Use C1512 to enable single or all POWs.
Configuration of the process output data
Code
C1511
Name
Configuring process output data
Index
0x5A18 (23064)
Subcode Lenze Access Data type
1 POW1 17 DRIVECOM control word (DRIVECOM−CTRL) rw FIX32
2 POW2 3 Setpoint 1 (NSET1−N1) rw FIX32
3 POW3 4 Setpoint 2 (NSET1−N2) rw FIX32
4 PAW4 5 Additional setpoint (PCTRL1−NADD) rw FIX32
þ Parameter set transfer
I Tip!
For a detailed description of the code, see ^ 59.