Codetabelle
Communication−relevant Lenze codes
10
l
59
EDS82ZAFIC EN 2.0
C1511:
Configuring process output data
Code
C1511
Name
Configuring process output data
Index
0x5A18 (23064)
Subcode Lenze Values Access Data type
1 POW1 17
see table below rw FIX32
2 POW2 3
3 POW3 4
4 POW 4 5
þ Parameter set transfer
The assignment of the max. 4 process output data words (POW) of the master to bit control
commands or setpoints of the controller can be configured freely using C1511.
) Note!
For reasons of compatibility, subcodes 5 and 6 can also be read and written
with modules from software version V3.0. However, this has no effect.
Selection Scaling
1 FIF control word 1 (FIF−CTRL1) 16 bits
2 FIF control word 2 (FIF−CTRL2) 16 bits
3 Setpoint 1 (NSET1−N1) ±24000 º ±480 Hz
4 Setpoint 2 (NSET1−N2) ±24000 º ±480 Hz
5 Additional setpoint (PCTRL1−NADD) ±24000 º ±480 Hz
6 Actual process controller value (PCTRL1−ACT) ±24000 º ±480 Hz
7 Process controller setpoint (PCTRL1−SET1) ±24000 º ±480 Hz
8 reserved
9 Torque setpoint / limit value (MCTRL1−MSET) 2
14
º 100 % rated motor torque
10 PWM voltage (MCTRL1−VOLT−ADD)
(
Only for special applications. Modifications only
after consulting Lenze!
11 PWM angle (MCTRL1−PHI−ADD)
12 reserved
13 FIF−IN.W1 16 bits or 0 ... 65535
14 FIF−IN.W2 16 bits or 0 ... 65535
15 FIF−IN.W3 0 ... 65535
16 FIF−IN.W4 0 ... 65535
17 DRIVECOM control word (DRIVECOM−CTRL) 16 bits