Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
7
l
41
EDS82ZAFIC EN 2.0
FIF status word 1 (FIF−STAT1) FIF status word 2 (FIF−STAT2)
Bit Assignment Bit Assignment
0 Current parameter set bit 0 (DCTRL1−PAR−B0) 0 Current parameter set bit 1 (DCTRL1−PAR−B1)
0
1
Parameter set 1 or 3 active
Parameter set 2 or 4 active
0
1
Parameter set 1 or 2 active
Parameter set 3 or 4 active
1 Pulse inhibit (DCTRL1−IMP) 1 TRIP, Q
min
or pulse inhibit active (DCTRL1−TRIP−QMIN−IMP)
0
1
Power outputs enabled
Power outputs inhibited
0
1
False
True
2 I
max
limit (MCTRL1−IMAX)
(If C0014 = 5: Torque setpoint)
2 PTC warning active (DCTRL1−PTC−WARN)
0
1
Not reached
Reached
0
1
False
True
3 Output frequency = frequency setpoint
(DCTRL1−RFG1=NOUT)
3
Reserved
Do not write to this bit!
0
1
False
True
4 Ramp function generator input 1 = ramp function
generator output 1
(NSET1−RFG1−I=O)
4 C0054 < C0156 and Q
min
threshold reached
(DCTRL1−(IMOT<ILIM)−QMIN)
0
1
False
True
0
1
False
True
5 Q
min
threshold (PCTRL1−QMIN) 5 C0054 < C0156 and NSET1−RFG1−I=O
(DCTRL1−(IMOT<ILIM)−RFG−I=O)
0
1
Not reached
Reached
0
1
False
True
6 Output frequency = 0 (DCTRL1−NOUT=0) 6 LP1 warning (fault in motor phase) active
(DCTRL1−LP1−WARN)
0
1
False
True
0
1
False
True
7 Controller inhibit (DCTRL1−CINH) 7 f < f
min
(NSET1−C0010 ... C0011)
0
1
Controller enabled
Controller inhibited
0
1
False
True
11...8 Device status (DCTRL1−STAT*1 ... STAT*8) 8 TRIP active (DCTRL1−TRIP)
Bit 11 10 9 8
0
1
False
True
0
0
0
0
0
1
0
0
Controller initialisation
Switch−on inhibit
9 Motor is running (DCTRL1−RUN)
0
0
0
1
1
0
1
0
Operation inhibited
Flying−restart circuit active
0
1
False
True
0 1 0 1 DC−injection brake active
10 Motor is running clockwise (DCTRL1−RUN−CW)
0
0
1
1
1
1
0
1
Operation enabled
Message active
0
1
False
True
1 0 0 0 Fault active
11 Motor is running counter−clockwise (DCTRL1−RUN−CCW)
1 1 1 1 Communication with basic device not
possible
0
1
False
True
12 Overtemperature warning (DCTRL1−OH−WARN) 12
Reserved
0
1
No warning
J
max
− 10 °C reached
13 DC−bus overvoltage (DCTRL1−OV) 13
Reserved
0
1
No overvoltage
Overvoltage
14 Direction of rotation (DCTRL1−CCW) 14 C0054 > C0156 and NSET1−RFG1−I=0
(DCTRL1−(IMOT>ILIM)−RFG−I=O)
0
1
CW rotation
CCW rotation
0
1
False
True
15 Ready for operation (DCTRL1−RDY) 15
Reserved
0
1
Not ready for operation (fault)
Ready for operation (no fault)
Tab. 7−2 Parameter structure FIF status word (FIF−STATx)