Diagnostics
LED status displays
7
l 34
EDS82ZAFVCxxx EN 4.0
7 Diagnostics
7.1 LED status displays
Function module E82ZAFVC001 Function module E82ZAFVC010
E82ZAFD001A* E82ZAFD101A*
Pos Colour Status Notes
1
off Function module is not supplied with voltage,
external voltage supply is switched off
green
blinking Function module is supplied with voltage but not connected to the controller.
Reason:
Standard device is
l switched off
l is being initialised
l not available
on Function module is supplied with voltage and is connected to the standard
device
red
blinking Internal error, Lenze setting has been loaded
on Internal error of the function module
2
off l No connection to the master
l Function module is not supplied with voltage.
green
blinking Dup_Mac_ID" test phase. Not yet connected to master (scanner).
on DeviceNet connection established.
red
blinking No communication due to time−out
on Critical bus error