Appendix
Code table
12
287
EDBCSXM064 EN 11.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0123 OC7 limit 90
Threshold for I x t warning (axis
module)
228
0 {1 %} 100 C0064 > C0123 ð fault message
OC7 (C0604)
C0124 OH5 limit 75
Threshold for temperature
monitoring inside the device
232
10 {1 %} 90 C0062 > C0124 ð fault message
OH5 (C0605)
C0125 Baud rate 0
Baud rate for operation via AIF
interface X1
0 9600 bit/s
Communication modules on AIF
interface X1:
l LECOM−A/B/LI 2102
l PROFIBUS−DP 2133
1 4800 bits/s
2 2400 bit/s
3 1200 bit/s
4 19200 bit/s
C0126 MONIT CE0 3
Fault response regarding the
monitoring of communication
via AIF interface X1.
l Via C2382 you can select
whether controller inhibit
(CINH) or quick stop (QSP) is
activated when a CE0 fault
occurs.
0 TRIP
A communication error activates
the CE0 response set.
2 Warning
3 Off Monitoring switched off.
C0127 OC8 limit 100
Threshold for I
2
x t warning
(motor)
237
0 {1 %} 120 I
2
x t > C0127 ð fault message
OC8 (C0606)
C0128 Tau motor 5.0
Thermal time constant of the
motor
237
0.5 {0.1 min} 25.0 For calculating the I
2
x t
disconnection
C0129 Charc.: Ix/Nx Reduction of the speed/torque
characteristic for UL−compliant
thermal motor monitoring (I
2
x t)
The reduced speed/torque
characteristic reduces the
permissible thermal load of
self−ventilated standard motors.
24
1 100
10 {1 %} 200
S1 torque characteristic I
1
/I
rated
This value also enables an
increase of the maximally
permissible utilisation.
2 40 S1 torque characteristics
n
2
/n
rated
With increasing speeds, the
maximally permissible
utilisation remains unchanged
(I
Mot
= I
rated
).