Mechanical installation
Important notes
4
38
EDBCSXM064 EN 11.0
4 Mechanical installation
4.1 Important notes
ƒ Axis modules of the ECS series provide IP20 enclosure and can therefore only be
used for installation in control cabinets.
ƒ If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):
Take suitable preventive measures , e.g. separate air duct, installation of filters,
regular cleaning.
ƒ Possible mounting positions:
Vertical at the mounting plate
DC bus connections (X23) at the top
Motor connection (X24) at the bottom
ƒ Maintain the specified clearances (above and below) to other installations!
If the ECSZS000X0B shield mounting kit is used, an additional clearance is
required.
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
Several modules of the ECS series can be installed in the control cabinet next to
each other without any clearance.
ƒ The mounting plate of the control cabinet
must be electrically conductive.
must not be varnished.
ƒ In case of continuous vibrations or shocks use shock absorbers.