Appendix
Code table
12
292
EDBCSXM064 EN 11.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0173 UG limit 11
Adaptation of the DC−bus
voltage thresholds:
l Check during commissioning
and adapt, if necessary.
l All drive components in DC
bus connections must have
the same thresholds.
– LU = Undervoltage
threshold
– OU = Overvoltage threshold
101
0 Mains = 230 V ± B Operation on 230 V mains with
or without brake unit
LU = 130 V, OU = 400 V
1 Mains = 400 V ± B Operation on 400 V mains with
or without brake unit
LU = 285 V, OU = 800 V
2 Mains = 460 V ± B Operation on 460 V mains with
or without brake unit
LU = 328 V, OU = 800 V
3 Mains = 480V − B Operation on 480 V mains
without brake unit
LU = 342 V, OU = 800 V
4 Mains = 480V + B Operation on 480 V mains with
brake unit
LU = 342 V, OU = 800 V
10 Mains = 230 V ± B Operation on 230 V mains with
or without brake unit
LU = C0174, OU = 400 V
11 Mains = 400 V ± B Operation on 400 V mains with
or without brake unit
LU = C0174, OU = 800 V
12 Mains = 460 V ± B Operation on 460 V mains with
or without brake unit
LU = C0174, OU = 800 V
13 Mains = 480V − B Operation on 480 V mains
without brake unit
LU = C0174, OU = 800 V
14 Mains = 480V + B Operation on 480 V mains with
brake unit
LU = C0174, OU = 800 V
C0174 UG min 60
Undervoltage threshold of DC
bus (LU)
101
15 {1 V} 342
C0175 UG−Relais Fkt 1
Charge relay behaviour with
undervoltage (LU) in the DC bus.
101
1 Standard Relay switches as a function of
LU.
2 One Time Relay switches when LU is
exceeded for the first time and
remains on.
3 Fixed On Charging current limitation is
inactive.
l Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.
l Setting for operation with
ECSxE power supply module.