Appendix
Code table
12
293
EDBCSXM064 EN 11.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0178 Op timer
Running time meter
Read only
0 {1 sec} 4294967295 Time when the controller was
enabled
C0179 Mains timer
Power−on time meter
Only display
0 {1 sec} 4294967295 Time when the mains was
switched on
C0183 Diagnostics
Drive diagnostics
Read only
l Indicates fault or status
information
l If several fault or status
information are to be shown
at the same time, the
information with the smallest
number is displayed
0 OK No fault
101 Initialisation phase
102 TRIP/trouble
103 Emergency stop activated
104 IMP message
105 Power off
111 Operation inhibit C0135
112 Operation inhibit AIF
113 Operation inhibit CAN
121 Controller inhibit via X6/SI1
122 Internal controller inhibit 1
123 Internal controller inhibit 2
124 Controller inhibit via STOP key of the
keypad
125 Controller inhibit via AIF
126 Controller inhibit via CAN
131 Fail QSP
141 Restart protection
142 Pulse inhibit High resistance power outputs
151 Quick stop (QSP) via terminal
152 Quick stop (QSP) via STOP key of the
keypad
153 Quick stop (QSP) via AIF
154 Quick stop (QSP) via CAN
160 PLC Stop PLC must be started.
250 Warning
C0195 BRK T act 99.9
{0.0}
Closing time of the motor
holding brake
105
0.0 {0.1 s} 99.9 During the time set the drive
continues to generate a torque.
After the set time has elapsed,
the status "mechanical brake
closed" is reached.