Electrical installation
The 9351 brake module
Connection to the 8200 vector controller (15 − 90 kW)
6
81
EDBMB935X DE/EN/FR 11.0
6.4 The 9351 brake module
6.4.1 Connection to the 8200 vector controller (15 − 90 kW)
K1
K1
U
V
W
M
3~
PE
K1
F1...F3
Z2
+UG
-UG
9351
Z1
K1
OFF
ON
RFR
RB
T1
T2
L1
L2
L3
Z3
F4
F5
28
E1
...
20
"
-UG
+UG
PE
"
"
"
PE
PE
"
"
"
"
L3
N
PE
L1
L2
9350br_006
Fig. 6 Connection of the 9351 brake module to controllers 8200 vector (15 − 90 kW)
Z1 Brake module
Z2 Controller
Z3 Mains choke
K1 Mains contactor
F1 ... F3 Mains fuses
F4, F5 DC−bus fuses (recommendation)
Mains voltage [V
eff
] Switching threshold [V] Switch position S1 Switch position S2
230 375 OFF OFF
400 ... 460 725 ON OFF
480
1)
765 ON ON
1)
Lenze setting in bold type