EasyManua.ls Logo

Lenze I51AE175F - EMC-Compliant Installation

Lenze I51AE175F
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EMC-compliant installaon
The drive system (inverter and drive) only complies with the EMC Direcve 2014/30/EU if it is installed
according to the guidelines for CE-typical drive systems.
These guidelines should also be followed in installaons requiring FCC Part 15 or ICES 001 compliance.
NOTICE
Electromagnec interference
Product and peripheral devices may be aected during operaon.
Please use suciently conducve shield connecons.
Connect the housing with shielding eect to the grounded mounng plate with a surface as large as
possible, e. g., inverters and RFI lters.
Use central earthing points.
The example below shows the eecve wiring:
A
B
C
D
E
A Shield connecon for control cables
B Control cable
C Mounng plate with conducve surface
D Shield connecon for motor cable
(alternavely: shield connecon on an
oponal motor shield plate)
E Motor cable with low capacity
EMC-compliant installaon must be implemented with shielded motor cables with low capacitance.
Capacitance per unit length:
C-core-core/C-core-shielding: < 75/150 pF/m ≤ 2.5 mm² (≥ AWG 14)
C-core-core/C-core-shielding: < 150/300 pF/m ≥ 4 mm² (≤ AWG 12)