Terminal data
Rated power P
rated
kW 0.37 ... 2.2 3 ... 4 3 ... 5.5 7.5 ... 11
Connecon descripon Mains connecon
Connecon X100
Connecon type Pluggable Non-pluggable
Max. cable cross-secon mm² 2.5 4 6 16
Max. cable cross-secon AWG 12 10 10 6
Stripping length mm 8 8 9 11
Stripping length in 0.3 0.3 0.35 0.43
Tightening torque Nm 0.5 0.6 0.5 1.2
Tightening torque lb-in 4.4 5.3 4.4 11
Required tool Screwdriver 0.5 x 3.0 Screwdriver 0.6 x
3.5
Screwdriver 0.8 x
4.0
Rated power P
rated
kW 0.37 ... 5.5 7.5 ... 11
Connecon descripon PE connecon
Connecon PE screw
Max. cable cross-secon mm² 6 16
Max. cable cross-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.4
Tightening torque Nm 2 3.4
Tightening torque lb-in 18 30
Required tool Torx key 20 Crossp screwdriver PZ2
Rated power P
rated
kW 0.37 ... 4 3 ... 5.5 7.5 ... 11
Connecon descripon Motor connecon
Connecon X105
Connecon type Pluggable Non-pluggable
Max. cable cross-secon mm² 2.5 6 16
Max. cable cross-secon AWG 12 10 6
Stripping length mm 8 9 11
Stripping length in 0.3 0.35 0.43
Tightening torque Nm 0.5 0.5 1.2
Tightening torque lb-in 4.4 4.4 11
Required tool Screwdriver 0.5 x 3.0 Screwdriver 0.6 x 3.5 Screwdriver 0.8 x 4.0
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
46