Fusing data
A residual current device (RCD) is oponal.
Fusing data for UL/NEC compliant installaons: 4Fusing data ^ 32
Inverter Fuse Circuit breaker RCD
Max.
SCCR
Characterisc
Max. rated
current
Max.
SCCR
Characterisc
Max. rated
current
Type
kA A kA A mA
I51AE137F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE155F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE175F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE211F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE215F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE222F 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE230F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51BE230F 65 gG/gL, gRL 25 65 B, C 25 ≥30 Typ B
I51AE240F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51BE240F 65 gG/gL, gRL 25 65 B, C 25 ≥30 Typ B
I51AE255F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51AE275F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51BE275F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51AE311F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51BE311F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
3-phase mains connecon 400 V "Light Duty"
Connecon diagrams
See "3-phase mains connecon 400 V". ^ 42
Terminal data
See "3-phase mains connecon 400 V" 4Terminal data ^ 43
Fusing data
A residual current device (RCD) is oponal.
Fusing data for UL/NEC compliant installaons: 4Fusing data ^ 32
Inverter Fuse Circuit breaker RCD
Max.
SCCR
Characterisc
Max. rated
current
Max.
SCCR
Characterisc
Max. rated
current
Type
kA A kA A mA
I51AE230F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51BE230F 65 gG/gL, gRL 25 65 B, C 25 ≥30 Typ B
I51AE240F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51BE240F 65 gG/gL, gRL 25 65 B, C 25 ≥30 Typ B
I51AE255F 65 gG/gL, gRL 25 65 B, C 25 ≥300 Typ B
I51AE275F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51BE275F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51AE311F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
I51BE311F 65 gG/gL, gRL 40 65 B, C 40 ≥300 Typ B
Electrical installaon
Mains connecon
3-phase mains connecon 400 V "Light Duty"