Fusing data
A residual current device (RCD) is oponal.
Fusing data for UL/NEC compliant installaons: 4Fusing data ^ 32
Inverter Fuse Circuit breaker RCD
Max.
SCCR
Characterisc
Max. rated
current
Max.
SCCR
Characterisc
Max. rated
current
Type
kA A kA A mA
I51AE125B 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE125D 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE137B 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE137D 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE155B 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE155D 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE175B 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE175D 65 gG/gL, gRL 16 65 B, C 16 ≥30 Typ B
I51AE211B 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
I51AE211D 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
I51AE215B 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
I51AE215D 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
I51AE222B 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
I51AE222D 65 gG/gL, gRL 32 65 B, C 32 ≥30 Typ B
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
37