Short Circuit Current Rangs (SCCR) with Semiconductor Fuses
(Tested per UL61800-5-1, reference UL le E132659)
These devices are suitable for standard installaon when used with Semiconductor Fuses. For single motor
installaon, if the fuse value indicated is higher than 400 % of the motor current (FLA), the fuse value has to
be calculated. If the value of the fuse is below two standard rangs, the nearest standard rangs less than
the calculated value shall apply.
Inverter Alternate Fuse (Semiconductor Fuse)
Mains Rated power Max. SCCR Max. rated current
kW hp kA A
230 V, 1-ph 0.25 0.33 100 15
230 V, 1-ph 0.37 0.5 100 15
230 V, 1-ph 0.55 0.75 100 40
230 V, 1-ph 0.75 1 100 40
230 V, 1-ph 1.1 1.5 100 40
230 V, 1-ph 1.5 2 100 40
230 V, 1-ph 2.2 3 100 40
230 V, 1/3-ph 0.25 0.33 100 15
230 V, 1/3-ph 0.37 0.5 100 15
230 V, 1/3-ph 0.55 0.75 100 40
230 V, 1/3-ph 0.75 1 100 40
230 V, 1/3-ph 1.1 1.5 100 40
230 V, 1/3-ph 1.5 2 100 40
230 V, 1/3-ph 2.2 3 100 40
230 V, 3-ph 4 5 100 50
230 V, 3-ph 5.5 7.5 100 50
480 V, 3-ph 0.37 0.5 100 6
480 V, 3-ph 0.55 0.75 100 15
480 V, 3-ph 0.75 1 100 15
480 V, 3-ph 1.1 1.5 100 15
480 V, 3-ph 1.5 2 100 15
480 V, 3-ph 2.2 3 100 15
480 V, 3-ph 3 4 100 40
480 V, 3-ph 4 5 100 40
480 V, 3-ph 5.5 7.5 100 40
480 V, 3-ph 7.5 10 100 50
480 V, 3-ph 11 15 100 50
Approved manufacturers for BCP fusing
Manufacturer Max. rated current Designaon
A
Mersen
6 A70QS6-14F
15 A60Q15-2
40 A70QS40-14F
50 A70QS50-22F
Electrical installaon
Connecon according to UL
Fusing data