Commissioning
Configuring the communication module
6.2.2 Automatically receiving an IP address
Clicking the Change button in the Settings tab (Fig. [6-1]
) opens the "Configure IP address"
dialog window.
Mark "Receive IP address automatically" in order to receive an IP address automatically
from the DHCP server:
[6-3] Automatically receiving an IP address
The input field for the standard gateway serves to manually enter a gateway address. By
default, the current values of the corresponding codes are displayed.
Setting the standard device code C00002 to "101: bind/unbind" or "102: bind/unbind"
copies the values and writes them to the corresponding codes:
The codes can also be set via the parameter list of the Servo Drive 9400 (All parameters
tab).
Tip!
You can use a ping command in the MS-DOS input window to test whether the
received IP address is valid or not.
Parameter Code
for slot MXI1 for slot MXI2
IP address C13000/1...4
C14000/1...4
Use of DHCP C13005 C14005
Note!
Observe the information given in chapter DHCP implementation in the Servo
Drive 9400 ( 34).