E94AYCEN communication manual (Ethernet)
Parameter data transfer
Telegram examples
46 L EDS94AYCEN EN 9.0 - 09/2012
Response
GCI message qualifier (GMQ) = 0x80 = 10000000B = "Response"
GCI header
GMT GSV GMQ GTI SIZE SIZE res res
0x01 0x82 0x80 0x00 0x14 0x00 0x00 0x00
Fixed Reading
parameters
Response Transactions ID Length of the user data = 20 bytes Reserved
User data area P0
Byte 1 Byte 2 Byte 3 Byte 4
Reserved Reserved Data type Reserved
0x00 0x00 0x03 0x00
INTEGER_32
User data area P1 User data area P2
Byte 1 Byte 2 Byte 3 Byte 4 Byte 1 Byte 2 Byte 3 Byte 4
Code Reserved Reserved Subcode Reserved Reserved
0x3D 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Code = 61 = 0x003D Subcode = 0
User data area P3 User data area P4
Byte 1 Byte 2 Byte 3 Byte 4 Byte 1 Byte 2 Byte 3 Byte 4
Parameter value of data type INTEGER_32 Reserved
0x00 0x00 0x00 0x2B 0x00 0x00 0x00 0x00
Read value = 0x0000002B = 43 [°C]