Device parameters and interfaces Leuze electronic
48 BPS 8 Leuze electronic
Setting the device-specific interface values
This sets the connection (interface) from the PC to the device and not the interface of the
device. For service interface operation, the settings here do not need to be edited.
If the connected device is not operated via the service protocol:
!
Use the left mouse button to select the device to be edited.
!
Right click and select Communication. In the Communication properties
window that
opens, carry out the respective changes.
If the settings were changed, the Leuze standard parameters can be reselected by clicking
on the
button.
Connector unit MA 8-01
The connector unit MA 8-01 is not relevant for the configuration and is thus not supported in
the BPS Configuration Tool.
8.1.3.3 Setting the Parameters
You now have commissioned the BPS 8 and are ready to configure it. Using the parameter
options made available by the BPS 8, you can configure the BPS 8 to suit your individual
area of application. Information about the various configuration options may be found in
chapter 8.1.6, page 52.
To understand what is happening during the parameter setting, chapter 8.1.5 briefly explains
the various parameter sets. The setting of the parameters then takes place in the service
operating mode, which is described in the following chapter.
8.1.4 Service operating mode
Setting the required parameters is carried out in the service operating mode. The operating
mode Service provides the following defined operating parameters on the external RS232
interface, no matter how the BPS 8 is configured for standard operation:
• transfer rate 9600 baud
• no parity
• 8 data bits
• 1 stop bit
• prefix: STX
• postfix: CR, LF