Leuze electronic Device parameters and interfaces
Leuze electronic BPS 8 61
TNT 35/7-24V
Parameters
Notice!
The switching input function Pos. measurement start/stop in the Function parameter
means:
• High level at the switching input starts the position measurement.
• Low level at the switching input stops the position measurement.
Parameter Description Value range Default Unit CR
Digital
I/O Mode
Defines whether the switching input
and output are activated via the
MA 8-01 or whether only the switching
input or only the switching output are
activated.
0: Not released
1: BPS 8 with MA 8-01
(switching input +
switching output)
2: Switching input
3: Switching output
1 ––
Invert
The parameter defines the logic of the
pending signal. In case of an inver-
sion, an external HIGH level is inter-
preted as an internal LOW level.
0: No (active high)
1: Yes (active low)
0 ––
Mode
This parameter controls the release of
the switching input.
0: Off
1: ON
1 ––
Debounce time
in [ms]
This parameter defines a debounce
time which is implemented in software.
0 … 255 5 ms –
Delay on time
in [ms]
The parameter influences the timing
during switch-on.
0 … 65535 0 ms –
Pulse duration
in [ms]
The parameter defines a minimum time
period before the signal is reset.
0 … 65535 0 ms –
Delay off time
in [ms]
The parameter defines a time delay for
the signal during switch-off.
0 … 65535 0 ms –
Function
The parameter specifies the function
which is to be activated or deactivated
by a change of state at the switching
input.
0: No function
2 –
–
1: Teach preset
Position
Logging
2: Start/stop position
measurement
Control
3: Stop position meas-
urement
Control
a
b
c
d
e
f
g
h
e
a
b