Converter Control MAG.DRIVE L2
55
GA 05.130/3.02 - 05/98
4.6.3 Settings pump
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Normal Operation Threshold for normal operation
corresponding to the 35 99 95 % r/w
frequency setpoint
Max. Accel. Time Monitor time for acceleration
and overload 600 3600 1000 s r/w
Pump Type Displays the installed pump type Installed pump type - r
4.6.4 Settings temperature management system
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
TMS Setpoint Setpoint Temperature- 20 70 63 °C r/w
Management-System
Set Pump
Enter
Normal Operation
95 %
Enter
Max. Accel. time
800 s
Enter
Pump Type
MAG 1600/2000 CT
Enter
Set TMS
Enter
TMS Setpoint
60 °C
Enter
r (read) = value can only be read
r /w (read/write) = value can be read and written