_TROUBLE SHOOTING GUIDE BOOK __
3. Relative humidity effect
•
In case of 35℃ (out air temp. condition)
- High humidity condition (RH 70 ~ 100%)
: Target coil temp. is lower than the standard humidity condition (RH 50~70%)
RH(%) 100~70 70~50 50~30 30~
T
air
-T
target
Target Coil Temp.
<-0.5 A+0.4 A+1.2
-0.5 ≤ & < 0.5 A A+0.8
0.5 ≤ & < 1.5 A-0.4 A+0.4
1.5 ≤ & < 2.5 A-0.8 A
2.5 ≤ & < 3.5 A-1.3 A-0.4
3.5 ≤ A-1.7 A-0.8
- Low humidity condition (RH 50 ~ 0%)
: Target coil temp. is less than the standard humidity condition (RH 50~70%)
RH(%) 100~70 70~50 50~30 30~
T
air
-T
target
Target Coil Temp.
<-0.5 A+1.2 A+2.0 A+2.8
-0.5 ≤ & < 0.5 A+0.8 A+1.6 A+2.4
0.5 ≤ & < 1.5 A+0.4 A+1.2 A+2.0
1.5 ≤ & < 2.5 A A+0.8 A+1.6
2.5 ≤ & < 3.5 A-0.4 A+0.4 A+1.2
3.5 ≤ A-0.8 A A+0.8
It is the function to set whether to use the humidity sensor. The outdoor unit considers the current outdoor
ambient humidity condition when making adjustments to the control values of the refrigeration cycle.
■ Setting the function
Function Option
Humidity Reference Fn 16 on, oFF
■ Option Selection
Setting Detail of function
on Humidity sensor use
oFF Not setting (Default)
■ Detailed information
•
The humidity sensor's real time reporting of the outdoor ambient humidity level is used in the Ad-
vanced Smart Load Control (FN14), Comfort Cooling (ID10), and Intelligent Defrost - Smart Heating
(core logic) to prepare the system for changes in the building load.
•
This function is used with heat pump and heat recovery.
•
Heating, Cooling and Dry modes is a change in the setting impact.
•
Cooling / Heating operation by using humidity sensor (Option "on")
- When used cooling operation of SLC function, it will improve energy efficiency because evapora-
tion temperature will be decreased
- When used heating operation in case of high humidity condition, deforest will be delayed because
target high/low pressure will be changed.
•
Activation function by using humidity sensor (Option "on")
Multi V Ⅳ Multi V Ⅳ Multi V 5 Multi V 5 Multi V 5
SLC
Comfort
Cooling
Dual Sensing
SLC
Dual Sensing
Comfort Cooling
Increased heating
time(Frost delay)
Operation
cooling ○ ○ ○ ○ X
Heating ○ X X X on
Consider
-
ation
Temperature ○ ○ ○ ○ ○
Humidity X X ○ ○ ○
4.15 Humidity Reference
· Ask an authorized technician to setting a function.