_TROUBLE SHOOTING GUIDE BOOK _
Checking Method (Flow Chart)
After power supplied,
the pressure on LGMV
is normal before
operating?
Voltage of 5V is output
from the PCB?
The location and
connection of connector
is normal on PCB?
PCB checking and replacement
Reconnection
Replace the pressure sensor
Checking start
No malfunction of the pressure
sensor
Yes
Yes
Yes
No
No
No
11. Humidity Sensor
If the humidity sensor has problem such as sensor open or short, no error display is shown at outdoor
unit.
Normally LGMV shows humidity ratio such as below display box of LGMV.
However, if the humidity sensor open/short occurred, it displays as "0".
In case of the sensor fault occurred, the system is operated not as the dual sensing SLC (Temperature
+ Humidity) but as the SLC (Only Temperature)
This means that system is normally operated without humidity function even if humidity sensor has
problem.
LGMV
Humidity : "0"