6.7 Comfort Cooling
It is function to reduce the ODU energy consumption by the continuous operation without thermo off.
■ Setting the function
Function Option
Comfort Cooling Id 10
seg1, seg2 : IDU No.
seg3, seg4 : 0, 1~3
■ Option Selection
seg1, seg2 seg3, seg4 seg3, seg4
1 ~ 64
0 No setting
1 Cooling capacity low, Power consumption low
2 Cooling capacity mid, Power consumption mid
3 Cooling capacity high, Power consumption high
•
Set EACH IDU : Select "Idu" → "Id10" → EACH → Select IDU No. → Set Value
•
Set All IDU : Select "Idu" → "Id10" → ALL → Set Value
■ Detailed information
•
This function is used with heat pump and heat recovery.
•
Possible setting condition
Indoor setting temperature
-
Indoor temperature < -2℃
•
Operation
-
Exist Indoor unit humid sensor : Use Indoor unit humid Value
-
Non Exist Indoor unit humid sensor : Use Default Value
-
Accurate superheat control using calculated values
· For detailed logic, please refer to the next appendix page.
•
Comfort Cooling means the superheat control of indoor unit.
: Changes the refrigerant flow rate of each indoor unit by EEV
•
Comfort Cooling is controlled by 2 factors.
-
1
st
: 『Room temperature (Tair)
-
Setting temperature (Ttarget)』
-
2
rd
: Relative humidity (default : outdoor humidity)
(Refer to indoor humidity if we applied standard III remote controller inside)
■ Cooling Operation Logic
1. Room temperature (T
air
)
-
Setting temperature (T
target
)
•
In case of standard humidity condition
-
condition.1 : superheat adjustment value is 0 (comfort cooling step.1 setting)
* refer to next slide (remote controller setting)
-
condition.2 : relative humidity is between 50% and 70%
T
air
-
T
target
Superheat Temp. Variation (℃)
< -0.5 +2
-0.5 ≤ & < 0.5 +2
0.5 ≤ & < 1.5 +1
1.5 ≤ & < 2.5 +1
2.5 ≤ & < 3.5 0
3.5 ≤0 0
2. Relative humidity effect
•
In case of high humidity condition (RH 100 ~ 70%)
-
No superheat temp. variation (not related with Tair
-
Ttarget )
•
In case of low humidity condition (RH 50 ~ 30%)
-
heat temp. variation was increased up to +3℃ (max)
RH(%) 100~70 70~50 50~30 30~
T
air
-T
target
Target Coil Temp.
< -0.5 0 +2 +3
-0.5 ≤ & < 0.5 0 +2 +3
0.5 ≤ & < 1.5 0 +1 +2
1.5 ≤ & < 2.5 0 +1 +2
2.5 ≤ & < 3.5 0 0 +1
3.5 ≤0 0 0 +1
2℃ High
0℃ Low
superheat
App. The Logic of Comfort Cooling