_TROUBLE SHOOTING GUIDE BOOK _
3.1 Failure Judge Method
3. EEV
Cooling
1. Main EEV
1) Basic control
- Variable path mode : Upper EEV Full Close / Lower EEV Full Open
- Low temperature cooling mode : Upper EEV Full Open / Lower EEV Close
2) Failure phenomenon
Upper EEV leakage
All the refrigerant flows into the upper EEV and decrease the capacity of the lower heat exchanger.
SC EEV Open to ensure SC degree
Lower EEV leakage
Flow rate is concentrated in check valve → Excessive pressure loss
Indoor refrigerant noise occurs
2. SC EEV
1) Basic control : SC / SH control
2) Failure phenomenon
SC EEV open failure : Outdoor SC can not be controlled
Indoor refrigerant noise occurs due to insufficient SC
Temperature is not lowered even if EEV is opened when discharge temperature emergency control
3. VI EEV
1) Basic control : Inverter start control, Vapor Injection control
2) Failure phenomenon
VI EEV open failure : CH21 error display, Compressor failure
Failure to reduce compressor different pressure during start-up
VI EEV Close failure : Failure to obtain the degree of discharge superheat,
CH21, Compressor failure → Liquid compression
* SC : Sub Cooling, SH : Super Heating
Heating
1. Main EEV
1) Basic control : Suction the degree of superheat control
2) Failure phenomenon
Upper EEV open failure
Excessive drop of low pressure, Upper and lower heat exchanger temperature difference 10 ℃ or
more
The refrigerant does not flow through the upper heat exchanger and the evaporation amount is
insufficient.
Lower EEV open failure
Excessive drop of low pressure, Upper and lower heat exchanger temperature difference 10 ℃ or
more
The refrigerant does not flow through the lower heat exchanger and the evaporation amount is
insufficient.
2. SC EEV
1) Basic control : Inverter emergency control
2) Failure phenomenon
SC EEV Open failure : EEV is open but discharge temperature is not lower
Open when compressor discharge temperature rises
3. VI EEV
1) Basic control : Inverter start control, Vapor Injection control
2) Failure phenomenon
VI EEV Open failure : CH21, Compressor failure
Failure to reduce compressor different pressure during start-up
VI EEV Close failure : Failure to obtain the degree of discharge superheat, CH21, Compressor failure
Liquid compression
* SC : Sub Cooling, SH : Super Heating