EasyManuals Logo
Home>LG>Remote Control>MultiSITE CRC1 Series

LG MultiSITE CRC1 Series User Manual

LG MultiSITE CRC1 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
56
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACNET POINTS
Name Type Read/Write
BACnet
Object ID
Device Facets
ZB_Zone7PairingStatus_M Multi State Input Read 272 No = 1, Yes = 2, Invalid = 3
ZB_Zone8PairingStatus_M Multi State Input Read 282 No = 1, Yes = 2, Invalid = 3
ZB_Zone9PairingStatus_M Multi State Input Read 292 No = 1, Yes = 2, Invalid = 3
ZB_
Zone10PairingStatus_M
Multi State Input Read 302 No = 1, Yes = 2, Invalid = 3
PipeTempCnfg_M Multi State Input Read 544 O󰀨 = 1, On = 2
ODUsilentMode_M Multi State Input Read 600 O󰀨 = 1, On = 2
SmartLoadCtrl_M Multi State Input Read 601 O󰀨 = 1, On = 2
OccStatus_M Multi State Input Read 602 O󰀨 = 1, On = 2
ODUstatus_M Multi State Input Read 603 O󰀨 = 1, On = 2
ODUType_M Multi State Input Read 604 MultiV = 1, Multi = 2, Single = 3, MultiV = 4
IDUType_M Multi State Input Read 605
Ceil Cass = 1, Duct = 2, CVT = 3, Commerical
Floor Standing = 4, Wall Mount = 5, ERV DX =
6, Console = 7, Rooftop = 8, ERV = 9, AWHP
= 10, Hydrokit = 11, Hyd Cascade = 12, Show
Case = 13, VAHU = 14, OAU = 15
TempUnits Multi State Value Write 51 Celsius = 1, Fahrenheit = 2
DisplayLanguage Multi State Value Write 4 English = 1, French = 2, Spanish = 3
FanSpeed Multi State Value Write 17
Low = 1, Med = 2, High = 3, Auto = 4, Slow = 5,
Lmed = 6, Mhigh = 7, Cool = 8, Power = 9
SystemMode Multi State Value Write 16
O󰀨 = 1, Cool = 2, Heat = 3, Fan = 4, Auto = 5,
Dry = 6
BACnetNetworkUnits Multi State Value Write 6 SI = 1, Imperial = 2
DisplayTimeFormat Multi State Value Write 5 AM/PM = 1, 24Hours = 2
DisplayColor Multi State Value Write 2
White = 1, Green = 2, Blue = 3 ,Grey = 4, Dark
Grey = 5
DisplayUseStandbyScreen Multi State Value Write 32 No = 1, Yes = 2, Occ Only = 3, Screen = 4
ZB_Zone1SnsrType Multi State Value Write 210
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone2SnsrType Multi State Value Write 220
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone3SnsrType Multi State Value Write 230
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone4SnsrType Multi State Value Write 240 None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone5SnsrType Multi State Value Write 250 None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone6SnsrType Multi State Value Write 260 None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7

Other manuals for LG MultiSITE CRC1 Series