EasyManua.ls Logo

LG MultiSITE CRC1 Series - Page 57

LG MultiSITE CRC1 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACNET POINTS
Name Type Read/Write
BACnet
Object ID
Device Facets
ZB_Zone7SnsrType Multi State Value Write 270
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone8SnsrType Multi State Value Write 280
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone9SnsrType Multi State Value Write 290
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
ZB_Zone10SnsrType Multi State Value Write 300
None = 1, Window = 2, Door = 3, Motion = 4,
Status = 5, Remove = 6, N/A = 7
DisplayShowOnO󰀨 Multi State Value Write 500 Show = 1, Hide = 2
DisplayShowMode Multi State Value Write 501 Show = 1, Hide = 2
DisplayShowSchedule Multi State Value Write 502 Show = 1, Hide = 2
DisplayShowMore Multi State Value Write 503 Show = 1, Hide = 2
DisplayShowSetTemp Multi State Value Write 504 Show = 1, Hide = 2
DisplayShowSpaceTemp Multi State Value Write 505 Show = 1, Hide = 2
DisplayShowFanSpeed Multi State Value Write 506 Show = 1, Hide = 2
DisplayShowHumidity Multi State Value Write 507 Show = 1, Hide = 2
TempSenseLoc Multi State Value Write 516 Remote Controller = 1, IDU = 2, 2TH = 3
IDUonO󰀨 Multi State Value Write 528 O󰀨 = 1, On = 2
AirowUpDown Multi State Value Write 531 O󰀨 = 1, On = 2
AirowLeftRight Multi State Value Write 532 O󰀨 = 1, On = 2
AirowCircular Multi State Value Write 533 O󰀨 = 1, On = 2
SingleDualSP Multi State Value Write 538 SingleSP = 1, DualSP = 2
OverrideMode Multi State Value Write 700
O󰀨 = 1, Cool = 2, Heat = 3, Fan = 4, Auto = 5,
Dry = 6
OverrideFanSpeed Multi State Value Write 701
Low = 1, Med = 2, High = 3, Auto = 4, Slow =
5, Low Med = 6, Med High = 7, Power Cool=8,
Power = 9
OverrideTimer Multi State Value Write 703
30 = 1, 60 = 2, 90 = 3, 120 = 4, 150 = 5, 180 =
6, 210 = 7, 240 = 8
SetbackMode Multi State Value Write 704
O󰀨 = 1, Cool = 2, Heat = 3, Fan = 4, Auto = 5,
Dry = 6
SetbackFanSpeed Multi State Value Write 705 Low = 1, Med = 2, High = 3, Auto = 4, Slow = 5,
Low Med = 6, Med High = 7, Power Cool = 8,
Power = 9
SingleSPdeadband Multi State Value Write 743 1°C = 1, 2°C = 2, 3°C = 3, 4°C = 4, 5°C = 5,
6°C = 6, 7°C = 7
CntrlrOccSensor Multi State Value Write 747 Disable=1,Enable=2

Other manuals for LG MultiSITE CRC1 Series

Related product manuals