58
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACNET POINTS
Name Type Read/Write
BACnet
Object ID
Device Facets
ControllerMinOccOnTime Multi State Value Write 748 10 Minutes = 1, 30 Minutes = 2, 60 Minutes = 3
Disable schedules Multi State Value Write 763 O = 1, On = 2
ZB_Snsr_Wn_Delay Multi State Value Write 766
0 Minutes = 1, 0.5 Minutes = 2, 1 Minute = 3, 2
minutes = 4, 5 Minutes = 5
ZB_Snsr_Win_Interlock Multi State Value Write 767
Disable = 1, IDUO/Automatic = 2, IDUO/
Manual = 3