Chapter 4 - Optional equipment 7200 Series UPS User Manual
Battery circuit breaker boxes Single Module and 1+1 Parallel System
document in response to "powersure ups"
Page 4-18
Issue 6
(03/98)
4520067T
+
+
-
-
Temp. sensing to UPS
Earth
Control/monitoring signals
TO UPS
TO BATTERY
Temperature
sensor
Maximum dimensions in mm:
Height = 470
Width = 300
Depth = 146
Control Board 4520067T terminal block X1
connections to the UPS auxiliary terminal block X3:
BCB System UPS
PCB
X1-5 = Temperature sensing signal = X3-2
X1-4 = Temperature sensing signal = X3-3
X1-3 = Control signal common = X3-4
X1-2 = C.B. status signal = X3-5
X1-1 = C.B. Control signal = X3-6
V<
+ -
3
2
1
X3
X4
X5
X6
X7
X8
X9
X 2
X10
1 2 3 4 5
X1
UPS CABINET
1
2
3
4
5
6
7
8
9
10
11
12
X3
- +
F13
BATTERY
CIRCUIT
BREAKER
SENSOR
Battery C.B.
Controller
Board ( 4520067T )
TEMPERATURE
(OPTIONAL)
4532029 V
TO BATTERY
Figure 4-M . Connections and layout of the battery circuit-breaker box