EasyManuals Logo

Liebert DM Series User Manual

Liebert DM Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
16 Chapter 2 Mechanical Installation
New Liebert_DM Series Air Conditioner User Manual
Total length of extended liquid pipe (m) = total length of liquid pipe (m) - 5m
Table 2-6 Adding refrigerant amount per meter of liquid pipes with different ODs
Liquid pipe OD (inch)
Adding refrigerant amount per meter (kg/m)
3/8
0.060
1/2
0.112
5/8
0.181
3/4
0.261
7/8
0.362
1-1/8
0.618
2.9 Check List
1. Proper clearance for service access is maintained around the AC unit.
2. The equipment is placed vertically and mounting fasteners are fastened.
3. The pipes between the indoor unit and outdoor unit are completed. The quick connector valves of the indoor unit
and outdoor unit are fully opened.
4. Condensate pump is installed (if required).
5. Drain pipe is connected.
6. Water supply pipe is connected to the humidifier (if required).
7. All pipe connectors are tight.
8. After installation, foreign materials in and around the equipment are removed (such as shipping materials,
construction materials, tools, and so on)
9. Rotate the fan blades by hand, and the fan rotate freely without unusual noise.
You can start electrical installation after confirming the preceding items.