46 Appendix 2 Parameter Setting Table
New Liebert_DM Series Air Conditioner User Manual
Menu
Parameter
Default
Setting range
System
Menu
Select
Options_CostSave
Mod_Sleep Mod
EngySave Cd Num
0
0 ~ 4
Sleep At 27°C 15°C ~ 40°C
Select
Options_Standby
Unit Status
SIG
SIG, HST, Standby
Switch Mod
Standby
Standby, Rotate
Rt Time
1d
1d ~ 7d
Rt At
12:00
0:00 ~ 23:00
Change Password
Level One
0001
0000 ~ 9999