3. Installation (up to 4 dampers) - no slave unit
3.1 Power supply to master unit
Provide 230 V power supply to master unit.
3.2 Connect local fire dampers (up to 4)
Connect local fire dampers power supply and position switches to master unit.
Maximum 4 fire dampers could be connected directly to the master unit (FDS-M).
FDS-M
L N
FDS-M
G0 D01 G0 D02 G0 D03 G0 D04
Fire damper 1
12
Fire damper 2
FDS-M
+C S2_1
Fire damper 1
S4 S2
S6_1
S1 S6
+C S2_2
S4 S2
S6_2
S1 S6
Fire damper 2
+C S2_3 S6_3 +C S2_4 S6_4
12
Power supply
0 230V 0 24V BA
G G0
Slave unit
AB
Master unit
3.1
3.2
3.3
3.4
+
FDS-M
Smoke detector
L1outL1in L2
2,2 k
Ω
Ceiling smoke detector
FDS-M
Smoke detector
53 4
2,2 k
Ω
Duct smoke detector
12
-+-+-+- +-+-+-+-
G
FDS-M
L N
FDS-M
G0 D01 G0 D02 G0 D03 G0 D04
Fire damper 1
12
Fire damper 2
FDS-M
+C S2_1
Fire damper 1
S4 S2
S6_1
S1 S6
+C S2_2
S4 S2
S6_2
S1 S6
Fire damper 2
+C S2_3 S6_3 +C S2_4 S6_4
12
Power supply
0 230V 0 24V BA
G G0
Slave unit
AB
Master unit
3.1
3.2
3.3
3.4
+
FDS-M
Smoke detector
L1outL1in L2
2,2 k
Ω
Ceiling smoke detector
FDS-M
Smoke detector
53 4
2,2 k
Ω
Duct smoke detector
12
-+-+-+- +-+-+-+-
G
Fire damper 1
12
Fire damper 2
FDS-M
+C S2_1
Fire damper 1
S4 S2
S6_1
S1 S6
+C S2_2
S4 S2
S6_2
S1 S6
Fire damper 2
+C S2_3 S6_3 +C S2_4 S6_4
Power supply
0 230V 0 24V BA
G G0
Slave unit
AB
Master unit
3.1
3.2
3.3
3.4
+
FDS-M
Smoke detector
L1outL1in L2
2,2 k
Ω
Ceiling smoke detector
FDS-M
Smoke detector
53 4
2,2 k
Ω
Duct smoke detector
12
-+-+-+- +-+-+-+-
G
Fire damper's cables
Supply 24V
Switches
Attention!
Color cables could change depending on motor
version. Numbering cables (1-2 for supply 24V, 1
to 6 for switches) stays the same on all motor ver-
sions.
+C
S2 _1
S6_1
+C
S2_2
S6_2
+C
S2_3
S6_3
+C
S2_4
S6_4
1 2 3 4
SERVOMOTOR SWITCHES
GD0
D01
GD0
D02
GD0
D03
GD0
D04
\ SEF
SERVOMOTORS
L N
230V AC
Fuse 6,3A