3 Troubleshooting
Service Manual
42
Table 3A Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No power supplied to the unit.
- No LED’s illuminated on the CON•X•US
Interface control board.
Check external line switch, fuse, or breaker.
Check position of ON/OFF switch. Turn switch to the
ON position.
Check 120 vac through the ON/OFF switch.
Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- Bad display, no LED’s illuminated.
• Check connection.
- Bad display.
Replace the display.
No Burner
Operation
- Main control board temperature set point
satisfied.
Review temperature setting.
- Remote thermostat satisfied.
Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3C of this manual.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions in this manual for corrective actions.
Unit Does Not
Modulate
Up to 100%
- Ramp delay active.
Check ramp delay parameter settings.
Turn ramp delay feature off. See this manual for
instructions on how to turn this feature off.
- Boiler controlled by BMS.
Check BMS parameter settings.