60
;AD7!===IgYfAUbiU`
OP CODE Meaning DATA TYPE ADDRESS Description
06h CB SBO CANCEL 43341 SBO Cancel Command.
Example) To send SBO cancel command to SOE GIPAM with station address number 1
after sending SBO select command
QUERY) 01 06 0D 0C 00 FF 0B 25
06h
SBO ARM TIMER
SETTING
43021 With ACK
Example) To send SBO ARM TIMER setting command to SOE GIPAM with station
address number 1(With ACK)
QUERY) 01 06 0B CC 07 D0 48 7D
06h
SBO ARM TIMER
SETTING
43001 No ACK.
Example) To send SBO ARM TIMER setting command to SOE GIPAM with station
address number 1(No ACK)
QUERY) 01 06 0B B8 07 D0 08 67
10h SOE EVENT SETTING
FAULT #1 43001 No ACK
FAULT #2 43002 No ACK
CB 43003 No ACK
SETTING / RESET 43004 No ACK
10h SOE EVENT SETTING
FAULT #1 43021 With ACK
FAULT #2 43022 With ACK
CB 43023 With ACK
SETTING / RESET 43024 With ACK
17.5.8 GMPC III
OP CODE Meaning DATA TYPE ADDRESS Description
10h Year 49801 00 - 99
Mon 49802 0 - 12