59
;AD7!===IgYfAUbiU`
OP CODE Meaning DATA TYPE ADDRESS Description
VERSION Information
04h SBO ARM TIME Read INT 33321
Example) To send Query for reading SBO ARM TIME to SOE GIPAM with station address
number 1
QUERY : 01 04 0C F8 00 01 B3 6B
05h RELAY FAULT RESET 3041
Control Command(No ACK)
05h CLEAR WH 3061
Control Command(No ACK)
05h CLEAR VARH 3081
Control Command(No ACK)
05h CLEAR ALL SOE DATA 3101
Control Command(No ACK)
05h CLEAR CB ON COUNT 3121
Control Command(No ACK)
05h CLEAR CB ON TIME 3141
Control Command(No ACK)
05h CLEAR Vo MAX 3161
Control Command(No ACK)
05h
CLEAR ALL BACKUP
DATA
3181
Control Command(No ACK)
05h RELAY FAULT RESET 3241
Control Command(With ACK)
05h CLEAR WH 3261
Control Command(With ACK)
05h CLEAR VARH 3281
Control Command(With ACK)
05h CLEAR ALL SOE DATA 3301
Control Command(With ACK)
05h CLEAR CB ON COUNT 3321
Control Command(With ACK)
05h CLEAR CB ON TIME 3341
Control Command(With ACK)
05h CLEAR Vo MAX 3361
Control Command(With ACK)
05h
CLEAR ALL BACKUP
DATA
3381
Control Command(With ACK)
06h CB ON/OFF Select 43341
06h CB ON/OFF Operate 43361
Example) To send CB ON SBO command to SOE GIPAM with station address number 1
1
st
Step) Send CB ON Select Command : 01 06 0D 0C 60 96 E3 0B
2
nd
Step) After receiving ACK response, Send CB ON Operate Command
: 01 06 0D 20 9F 69 23 72
Example) To send CB OFF SBO command to SOE GIPAM with station address number 1
1
st
Step) Send CB OFF Select Command: 01 06 0D 0C 61 69 A2 DB
2
nd
Step) After receiving ACK response, Send CB OFF Operate Command
: 01 06 0D 20 9E 96 62 A2