OP CODE Meaning DATA TYPE ADDRESS Description
Operating Voltage Value
in Time Delay char. of
OVGR
BCD CODE 33261(H) .XX(Higher 1 BYTE)
Operating Voltage Value
in Instantaneous char. of
OVGR
BCD CODE 33261(L) .XX(Lower 1 BYTE)
OVGR Operating Time BCD CODE 33262
0X.XX
Higher BYTE : 0X
Lower BYTE : .XX
Selecting OVGR
Function
BCD CODE 33263 0X(Lower 1 BYTE)
SGR Operating Current BCD CODE 33264(H) X.X(Higher 1 BYTE)
SGR Operating voltage BCD CODE 33264(L) X.X(Lower 1 BYTE)
SGR Operating Time BCD CODE 33265
XX.X0
Higher BYTE : 0X
Lower BYTE : .XX
Selecting SGR Function BCD CODE 33266 0X(Lower 1 BYTE)
RESERVED BCD CODE 33267 0X(Higher 1 BYTE)
04h
SOE ENABLE and TIMER
Status Information
RELAY Operation EVENT
ENABLE
INT 33281 BIT Operation
CB Status Change
EVENT ENABLE
INT 33282
BIT Operation
(Lower 1 BYTE)
7 : local on
6 : local off
5 : remote on
4 : remote off
3,2 : 0
1 : on Input
0 : off Input
RESET/CLEAR EVENT
ENABLE
INT 33283
BIT Operation
(Lower 1 BYTE)
7 : relay setting
6 : fault reset
5 : Vo max
4 : CB ON time
3 : CB ON counter
2 : SOE buffer
1 : varh
0 : wh
GIPAM Internal TIMER
Calibration
INT 33284
04h DEVICE Name and STRING 33301 Example)33301-33306 M