57
;AD7!===IgYfAUbiU`
OP CODE Meaning DATA TYPE ADDRESS Description
OCR
Operating Current Value
in Instantaneous char. of
OCR
BCD CODE 33221(L)
XX
(Lower 1 BYTE)
OCR CURVE BCD CODE 33222 0X (Lower 1BYTE)
Operating Time of OCR BCD CODE 33223
0X.XX
Higher BYTE : 0X
Lower BYTE : .XX
Operating Current Value
in Time Delay char. of
OCGR
BCD CODE 33224(H)
.XX
(Higher 1 BYTE)
Operating Current Value
in Instantaneous char. of
OCGR
BCD CODE 33224(L)
X.X
(Lower 1 BYTE)
OCGR CURVE BCD CODE 33225 0X(Lower 1BYTE)
Operating Time of OCGR BCD CODE 33226
0X.XX
Higher BYTE : 0X
Lower BYTE : .XX
Selecting OCGR
Function
BCD CODE 33227 0X(Lower 1BYTE)
04h OVR/UVR SETTING
OVR Operating Voltage BCD CODE 33241
0X.XX
Higher BYTE : 0X
Lower BYTE : .XX
OVR Operating Time BCD CODE 33242
XX.X0
Higher BYTE : 0X
Lower BYTE : .XX
Selecting OVR Function BCD CODE 33243 0X(Lower 1 BYTE)
UVR Operating Voltage BCD CODE 33244 .XX(Lower 1 BYTE)
UVR Operating Time BCD CODE 33245
XX.X0
Higher BYTE : 0X
Lower BYTE : .XX
Selecting UVR Function BCD CODE 33246 0X(Lower 1 BYTE)
04h OVGR/SGR SETTING