40
;AD7!===IgYfAUbiU`
a) Set Data of Measuring Part
Command 0Dh
Sub Command 00h
Setting CT Ratio Refer to setting DIP Switch in the GIPAM Manual
Setting PT Ratio Refer to setting DIP Switch in the GIPAM Manual
Setting System wiring
Setting Relay enables
Number of CB operation
Accumulated time
that CB is closed (100msec)
Data Check Sum Check Sum
- Checksum(1Byte) = (Command(1Byte) + Sub Command (1Byte) + Data(10Byte) / 256
⇒ The residual
※ Checksum is the sum of each bytes not to include OVERFLOW.
b) OCR/OCGR Setting Data
Command 0Dh
Sub Command 01h
Current value of
Time Delay char. for OCR
X.X
Current value of
Instantaneous char. for OCR
XX
Time/Char. Curve for OCR 0X
0X (Up to a decimal point )
Operating time for OCR
.XX (Down to a decimal point)
Current value of
Time Delay char. for OCGR
.XX
Current value of
Instantaneous char. for OCGR
X.X
Time/Char. Curve for OCR 0X
0X (Up to a decimal point)
Operating time for OCR
.XX (Down to a decimal point)
Selecting OCGR Function 0X
Data Check Sum Check Sum
- Each item is represented as BCD that has a decimal point.