Chapter 15 The PID function of K200S MASTER-K
15-16
(Continued)
Device
offset
Name Description Range
+ 11 EN_I Enable / disable the integral operation 0 or 1
+ 12 EN_P Enable / disable the proportional operation 0 or 1
+ 13 BIAS The bias value for offset compensation 0 ~ 4000
+ 14 PV The present value
+ 15 SV The set value data 0 ~ 4000
+ 16 F/R Select forward or reverse operation 0 or 1
+ 17 MAN Enable / disable manual operation 0 or 1
+ 18 STAT Shows an error code when error occurs
+ 19 MV The manipulation value (MV) output
+ 20 ERR The deviation between PV and SV
+ 21 P_VAL (LOW)
+ 22 P_VAL (HIGH)
+ 23 I_VAL (LOW)
+ 24 I_VAL (HIGH)
+ 25 P_VAL (LOW)
+ 26 P_VAL (HIGH)
Reserved for internal calculation
+ 27 Bi
+ 28 Ad
+ 29 Bd
+ 30 AO
+ 31 PV_OLD
+ 32 ACTUATOR_OUT
+ 33 REAL_MV (LOW)
+ 34 REAL_MV (HIGH)
+ 35 CORRUPT/STAGE
+ 36 TEMP_PV
System use only
1) S_TIME
The scan time in PID operation means the interval of sampling the present value (PV). In
general, the PID operation shows best performance when the S_TIME is synchronized
with external enable input. (The input condition of PIDCAL instruction)
The range of S_TIME is 0.1 ~ 10 seconds. However, when input S_TIME data into PLC
device, it is scaled up 10 times for more precise setting. Therefore, the actual range of
input data is 1 ~ 100.