S100 PROFInet Option Manual
23
PNU
R/W
Description
967
R
Displays the control word (STW1) value that is
currently input via the PROFInet communication
network.
968
R
Displays the status word (ZSW1) value that is currently
input via the PROFInet communication network.
972
R/W
The S100 communication module is reset when the
parameter value is changed to “1” from “0.”
61000
R
Displays the device name of the S100 PROFInet
communication module.
61001
R
Displays the IP address of the S100 PROFInet
communication module.
61002
R
Displays the MAC address of the S100 PROFInet
communication module.
61003
R
Displays the gateway IP address of the S100
PROFInet communication module.
61004
R
Displays the subnet mask of the S100 PROFInet
communication module.
1000
R/W
S100 Parameter Access Address (communication
address for reading or writing inverter parameters)
1001
R/W
S100 Parameter Access Data (data value of inverter
parameters for reading or writing)
1002
R/W
S100 Parameter Access Command
1: write
2: read
1003
R/W
S100 Parameter Access Acknowledge
0: Not completed
1: OK completed
2: Not OK completed