(2
) “S(U)type
(a) Parameter setting
Parameter
Description Device area per channel
Remark
Value Setting
Ch 0 Ch 1 Ch 2 Ch 3
Ch 4 Ch 5 Ch 6 Ch 7
Counter
mode
h0000 Linear count
K300 K330 K360 K390
Word
h0001 Ring count
K2220 K2250 K2280 K2310
Pulse input
mode
setting
h0000 1 phase 1 input 1 multiplication
K301 K331 K361 K391 Word
h0001 1 phase 2 input 1 multiplication
h0002 CW / CCW
K2221 K2251 K2281 K2311 Word
h0003 2 phase 4 multiplication
Comp.
Output 0
mode
setting
h0000 (Magnitude) <
K302 K332 K362 K392
Word
h0001 (Magnitude)
h0002 (Magnitude) =
h0003 (Magnitude)
h0004 (Magnitude) >
K2222 K2252 K2282 K2312
h0005 (Range) Include
h0006 (Range) Exclude
Comp.
Output 1
mode
setting
h0000 (Magnitude) <
K303 K333 K363 K393
Word
h0001 (Magnitude)
h0002 (Magnitude) =
h0003 (Magnitude)
h0004 (Magnitude) >
K2223 K2253 K2283 K2313
h0005 (Range) Include
h0006 (Range) Exclude
Internal
preset value
setting
-2,147,483,648 ~ 2,147,483,647
K304 K334 K364 K394
DWord
K2224 K2254 K2284 K2314
External
preset value
setting
-2,147,483,648 ~ 2,147,483,647
K306 K336 K366 K396
DWord
K2226 K2256 K2286 K2316