Chapter 6 CPU Functions
6- 2
6.2 Parameter Setting
This paragraph describes how to set parameters.
6.2.1 Basic parameter setting
Clicking Basic Parameter in the project window shows the following window.
There are three main options ; Basic Operation Setup ,Device Area Setup and Error Operation
Setup”.
Category
Item
Description
Note
Basic
operations
Fixed period
operation
Set the time of fixed period operation.
1~999
Watchdog timer
Set the time of scan watchdog.
10~1000
Standard input filter
Set the time of standard input filter.
1,3,5,10,20,70,100
Output during
debugging
Set whether to allow output actually during
debugging operation.
Allowance/Prohibition
Keep output when
an error occurs
Set whether to preserve output holding
function set in I/O parameter in case of error.
Allowance/Prohibition
Delete all areas
except latch when an
error occurs
Set whether to clear each device that is not
designated as a latch area in case of error
Allowance/Prohibition
Device
area
Select latch area
Set the latch area of each device.
-
Error
operation
Operation resumes
in case of operation
error
Set whether to pause or resume operation in
case of operation error.
Pause/Resume