Chapter 8 Power Module
8-5
8.4 Current Consumption/Power Calculation Example
Here describes which power module should be used in case of XGK system that the following module is
mounted.
Voltage system
Type Model Number of setup
5V 24V
CPU module XGK-CPUH 1 0.96A -
12 Slot main base XGB-B12M - - -
Input module XGI-D24A 4 0.2A -
Output module XGQ-RY2A 4 2.0A -
FDEnet module XGL-EDMF 2 1.3A -
Profibus-DP XGL-PMEA 2 1.12A -
Calculation 0.96+0.2+2+1.3+1.12 -
Current consumption
Result 5.58A -
Calculation 5.58×5V -
Energy consumption
Result 27.9W -
As the value of 5V current consumption is 5.58A, use XGP-ACF2(5V:6A) or XGP-AC23(5V:8.5A). If used XGP-
ACF1(5V:3A), the system does not operate.