Chapter 7 I/O Module
7-10
7.2.8 16 point AC110V Input Module
AC input module Model
Specification
XGI-A12A
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage AC100-120V(+10/-15%) 50/60 ㎐(±3 ㎐) (distortion rate < 5%)
Rated input current About 8 ㎃ (AC100,60 ㎐), About 7 ㎃ (AC100, 50 ㎐)
Inrush current Max. 200 ㎃ 1㎳ (AC132V)
Input Derating Refer to the below Derating diagram.
On Voltage/Current AC80V or higher / 5 mA or higher (50 ㎐, 60 ㎐)
Off Voltage/Current AC30V or lower / 1 mA or lower (50 ㎐, 60 ㎐)
Input resistance About 12 kΩ(60 ㎐), About 15 kΩ(50 ㎐)
Off → On
15 ms or less (AC100V 50 ㎐, 60 ㎐)
Response
time
On → Off
25 ms or less (AC100V 50 ㎐, 60 ㎐)
Insulation pressure AC1780V rms/3 Cycle (altitude 2000m)
Insulation resistance 10 ㏁ or more by megger
Common Method 16 point / COM
Proper cable size Twisted pair 0.3~0.75 ㎟ (external diameter 2.8mm or less)
Proper compressed terminal R1.25-3 (not allowed to use a sleeve attached compressed terminal.)
Current consumption (㎃) 30mA
Operation indicator Input On, LED On
External connection method 18 point terminal block connector (M3 X 6screw)
Weight 0.13 kg
Circuit configuration
Terminal
block
Contact
TB
1
P0
TB2 P1
TB3 P2
TB4 P3
TB5 P4
TB6 P5
TB7 P6
TB8 P7
TB9 P8
TB10 P9
TB11 PA
TB12 PB
TB13 PC
TB14 PD
TB15 PE
TB16 PF
TB17 COM
TB18 NC
AC120V
100
80
60
40
0 10 20
30
40
50
55
On
Rate
(%)
Ambient temperature ( )℃
90
70
50
AC132V
00
06
0D
COM
01
02
03
04