Macurco CD-6B Manual (Rev-1.0) Eng
REV 1.0 [34-2900-0510-2 ] 26 | Page
A1rtAlarm 1 Relay Test, energized for 5 seconds, display flashing A1rt
A2rtAlarm 2 Relay Test, energized for 5 seconds, display flashing A2rt
A3rtAlarm 3 Relay Test, energized for 5 seconds, display flashing A3rt
gtSGas Test, 3 minutes, display flashes between gtS and current gas reading, green LED blinking, relays are
not triggered by gas reading, green LED continues blinking for another minute then becomes solid green
NOTE: If an alarm relay setting has been disabled diS”, the test selection will not be displayed in the test menu.
To perform a manual operation test,
1. From normal operation mode press the NEXT button 2 times to get to the Test Mode (tSt).
2. Press the ENTER button once to get into the Test Menu.
3. Press the NEXT button to scroll through the five test options.
4. Press ENTER to initiate the selected test.
5. Once the test is complete, the display will return to a steady display.
6. Press NEXT until “End” is displayed to exit the test menu.
7. Press ENTER to return to normal mode.
7.2 Calibration Kit
WARNING
The following steps must be performed when conducting a calibration verification test (bump
test) and calibration
to ensure proper performance of the monitor. Failure to do so may
adversely affect product performance.
When performing a calibration verification test (bump test) and calibration only use
certified calibration gas at the required concentration level.
Do not test with expired calibration gas.
Do not cover or obstruct display or visual alarm cover.
Ensure sensor inlets are unobstructed and are free of debris
Failure to follow instructions outlined in this user manual can result in sickness or death.
A Field Calibration Kit, CD6B-FCK, is needed to complete a field calibration. These are available through local
distribution.
Gas cylinder
o 17L 400 ppm carbon dioxide (CO
2
) in air
o 17L 5% volume carbon dioxide (CO
2
) in air
Gas regulator 0.2 LPM
About two feet of tubing
CD-6-CH calibration hood
Carry case
FCK Information
Several detectors can be calibrated with one FCK. The only limitation is the amount of gas in the cylinder. The 17-
liter cylinder has approximately 85 minutes of continuous calibration run time. Replacement cylinders are available.