Page 63Version 2023-06-15 Fire damper - FDMR
TPM 140/19
For connection of following duct → see page 90
Installation frame can be installed on the damper or delivered separately
Installation procedure of the installation frame for FDMR → see manual
Installation frame R1 - wall th. 100 mm
Installation frame R2 - wall th. 150 mm
In solid wall construction - installation frame R1, R2
EIS 90
1 FDMR
2 Installation frame
3 Bracket with fasteners (delivered with frame)*
4 Fill the gaps with glue PROMAT K84
5 Duct
6 Clamp with threaded rod → see pages 87 to 89
7 Solid wall construction
100 (R1)
150 (R2)
Ø
D
ØD+145
+3
(installation opening)
Ø
D+160
Ø
D+145
+3
(
installation opening)
* Bracket with fasteners for 1 damper
FDMR diameter
Number of
brackets
Number of
screws
D ≤ 400 4 8
400 < D ≤ 800 8 16