Fire damper - FDMRPage 64 Version 2023-06-15
TPM 140/19
In solid wall construction - 2 dampers in one opening- installation frame R1
EIS 90
For connection of following duct → see page 90
Installation frame can be installed on the damper or delivered separately
Installation procedure of the installation frame for FDMR → see manual
It is possible to install up to 4 dampers symmetrically in one opening
2xØ
D+320
2xØD+285
+3
+20
(installation opening)
100
Ø
D
ØD+160
Ø
D+145
+3
(installation open-
ing
)
20
100
2xØD+320
2xØ
D+285
+3
+20
(installation opening)
20
Ø
D
Ø
D+145
+3
(installation open-
ing)
Ø
D+160
1 FDMR
2 Installation frame
3 Bracket with fasteners (delivered with frame)*
4 Fill the gaps with glue PROMAT K84
5 Duct
6 Clamp with threaded rod → see pages 87 to 89
7 Solid wall construction
8 Mineral wool board - min. density 140 kg/m³ (e.g. PROMAPYR-T150)
* Bracket with fasteners for 1 damper
FDMR diameter
Number of
brackets
Number of
screws
D ≤ 400 4 8
400 < D ≤ 800 8 16