EasyManua.ls Logo

Mandik FDMR - Page 80

Mandik FDMR
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fire damper - FDMRPage 80 Version 2023-06-15
TPM 140/19
For connection of following duct → see page 90
The duct must be suspended or supported on both sides of the damper acc. to national rules
Load of the suspension system depends on weight of the fire damper and duct system → see page 87
Max. distance between two suspension systems is 1500 mm
Following air-conditioning duct must be suspended or supported so that all load transfer from the following duct to the fire damper is
absolutely excluded. Adjacent duct must be suspended or supported, as required by the duct suppliers
Installation frame can be installed on the damper or delivered separately
Installation procedure of the installation frame for FDMR → see manual
Outside solid ceiling construction - concreting - installation frame R5
1 FDMR
2 Installation frame - apply HILTI CFS-S ACR mastic at the entire area and
glue it to the fire separating construction
3 Fill the gaps with glue PROMAT K84
4 Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm
5 Clamp with threaded rod → see pages 87 to 89
6 Solid ceiling construction
7 Concrete B20
8 Rebar - steel rod Ø 6 mm, mesh hole 100 mm
9 Holes for fixing the frame with threaded rods or steel anchors (frame
fixing material not included)
50...150
EIS 90
≥ 110*
≤ 750
50...150
100
100
30
A
4 x
Ø
12
ØD
X
A
* min. 110 mm - Concrete
min. 125 mm - Aerated concrete
X = ØD+120 for dampers ØD 100-200 mm
X = ØD+167 for dampers ØD 225-800 mm

Other manuals for Mandik FDMR

Related product manuals