126 Part Number 80-1505-3 6/11
SAFETY LIMIT#1
Freeze time exceeds 60 minutes for 6 consecutive
freeze cycles
Possible Cause Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
page 151.
Water System
Dirty/defective water level probe
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water fill valve
Dirty/defective water dump valve
Defective water pump
Loss of water from sump area
Electrical System
Low incoming voltage
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Defective fan cycling control
Defective fan motor
Miscellaneous
Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control
Defective harvest valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensable in refrigeration system
Plugged or restricted high side refrigerant lines or
component
Restricted air flow/dirty condenser fins
High inlet air temperature
Condenser discharge air recirculation